RG Flex Telecom Power Cable

Cablcon (formerly Jupiter Communications) exclusively offers RG Flex cables, a family of DC Power Cables that have been tested and certified by Telcordia and meet the functional performance requirements of GR-347 Issue 3, TPR.9212 and ATIS-0600017.2020. RG Flex cables, also known as Central Office Power Cables, are Telcordia-certified meaning that the L2, L3, and L4 power cables are suitable for use in all telecommunications applications including central offices, remote terminal applications, data center and outside plant remote cabinets that house electronics equipment.

List 2 DC Power Cable - Available Cable Constructions

Size
AWG or kcmil

Stranding
Number/dia (inch)

Conductor
diameter (inches)

Insulation min.
Thickness (mils)

Nominal insulation
Diameter (inches)

Max.d.c.res. @ 20°C
(ohms/ mft.)

Approx. Weight
lbs./mft.

18 7/0.0157 0.0472 30 0.106 7.163 11
16 7/0.0197 0.059 30 0.118 4.81 15
14 41/0.0100 0.074 45 0.181 2.728 25.4
12 65/0.0100 0.093 45 0.197 1.719 34.8
10 105/0.0100 0.12 45 0.228 1.079 50
8 41/0.0201 0.147 60 0.28 0.68 77.8
6 65/0.0201 0.192 60 0.319 0.436 112.6
4 105/0.0201 0.257 60 0.394 0.274 169.4
2 165/0.0201 0.309 60 0.445 0.172 248.5
1 210/0.0201 0.346 80 0.52 0.137 327
1/0 266/0.0201 0.398 80 0.575 0.109 405.2
2/0 342/0.0201 0.455 80 0.63 0.087 516.5
4/0 532/0.0201 0.571 80 0.748 0.055 754.9
350 882/0.0201 0.752 95 0.965 0.034 1194.1
500 1221/0.0201 0.894 95 1.102 0.023 1606.5
750 1850/0.0201 1.067 110 1.323 0.016

2414.4

View spec sheet as a PDF

List 3 DC Power Cable - Available Cable Constructions

Size
AWG or kcmil

Stranding
Number/dia (inch)

Conductor
diameter (inches)

Insulation min.
Thickness (mils)

Nominal insulation
Diameter (inches)

Nominal braid
diameter (inches)

Max.d.c.res. @ 20°C
(ohms/ mft.)

Approx. Weight
lbs./mft.

14 7/0.0240 0.071 45 0.173 0.24 2.731 33.6
12 7/0.0303 0.09 45 0.193 0.256 1.719 48.6
10 7/0.0386 0.113 45 0.217 0.279 1.079 64.1
8 7/0.0484 0.143 60 0.276 0.338 0.677 97.1
6 7/0.0610 0.181 60 0.31 0.378 0.427 127.6
4 7/0.0772 0.228 60 0.358 0.425 0.268 189.8
2 7/0.0972 0.286 60 0.417 0.484 0.169 272.6
1 19/0.0654 0.327 80 0.488 0.57 0.134 355
1/0 19/0.0744 0.366 80 0.539 0.61 0.106 432
2/0 19/0.0839 0.417 80 0.587 0.661 0.084 534.4
4/0 19/0.1055 0.524 80 0.693 0.771 0.052 794.4
350 37/0.0972 0.665 95 0.87 0.941 0.032 1258
500 37/0.1142 0.803 95 1.008 1.078 0.021 1769.8
750 61/0.1110 0.976 110 1.213 1.283 0.015 2574.6

View spec sheet as a PDF

List 4 DC Power Cable - Available Cable Constructions

Size
AWG or kcmil

Stranding
Number/dia (inch)

Conductor
diameter (inches)

Insulation min.
Thickness (mils)

Nominal insulation
Diameter (inches)

Nominal braid
diameter (inches)

Max.d.c.res. @ 20°C
(ohms/ mft.)

Approx. Weight
lbs./mft.

8 41/0.0201 0.147 60 0.28 0.342 0.68 98.1
6 65/0.0201 0.192 60 0.315 0.381 0.436 135.3
4 105/0.0201 0.257 60 0.39 0.452 0.274 195.5
2 165/0.0201 0.309 60 0.441 0.508 0.172 278.5
1 210/0.0201 0.346 80 0.512 0.59 0.137 361
1/0 266/0.0201 0.398 80 0.571 0.641 0.109 442.8
2/0 342/0.0201 0.455 80 0.626 0.7 0.087 548.1
4/0 532/0.0201 0.571 80 0.736 0.814 0.055 804.1
350 882/0.0201 0.752 95 0.953 1.027 0.034 1254.9
500 1221/0.0201 0.894 95 1.087 1.157 0.023 1676
750 1850/0.0201 1.067 110 1.307 1.382 0.016 2499.6

View spec sheet as PDF

Cablcon (formerly Jupiter Communications) is the exclusive distributor for all RG Flex power cables in North America.